AS4284 Building Facades Testing
OmniTest’s curtain wall rig is designed to test the performance of building facades in compliance with Australian Standard AS 4284:2008 – Testing of building facades.
Methodology/Test Sequence:
Preliminary test (required):
- Static Pressure: the test sample shall be subjected to positive and negative SLS design wind pressures for the duration of 10 seconds.
- Water: The sample shall be exposed to water under static and cyclic pressures
Structural test at Serviceability limit state (required):
Determines the wind-loaded span of the specimen under a specified or predetermined pressure, measured in Pascals.
Air Infiltration (optional):
Determines the resistance to air infiltration when the specimen is under pressure and measured through base and total readings.
Water penetration (required):
- Static Pressure: The specimen is sprayed uniformly with water over a period of 15 minutes.
- Cyclic Pressure: The specimen is exposed to water in three stages under specified cyclic pressures determined in accordance with geographical location.
Strength test at Ultimate Limit State (required):
The specimen is subjected to a load that will determine its capacity to withstand differential pressure.